The programmable drive is located inside the main skirting of the table. Face the table from the side with the control box. Remove two of the screws that secure the outer skirt to the main frame. One screw is at the foot end, the other is facing you.

Tables after May 2008 have a higher carrier frequency which necessitates a higher fixed boost (parameter 28) setting. This is need is usually realized when an older table and an “after May 2008” table are at the same location and the newer one runs slower at the same speed dial setting as the original table.
DO THIS… SHOWS THIS… EXPLANATION….
1. Press MODE “00.0” wants password
2. Use ARROWS to display “25” and press MODE “P (#)” you are in the program menu
3. Use ARROWS to select parameter “P28” P19 is for “fixed boost”
4. Press MODE “ ” original setting
5. Use UP ARROW to change to “5.6” new setting
6. Press MODE to store the new value